DRY-AIR STAINLESS STEEL SPECIFICATION SHEET
DAP-HC-144 NOMINAL 12 TON UNIT
The DRY-AIR Stainless Steel HGR Series 144 is built with a 5 Row Field Cleanable Evaporator Coil. This unit has two hermetically sealed dual compressors, and simultaneously rejects heat to the pool, room and outdoor condenser. This unit can be built vertically in Stainless Steel. (Horizontal is available in non-stainless steel.) Economizer fresh-air purge option available. The available options are air cooled, water cooled and as a ground source Geothermal Heat Pump Application. All 1-12 tons come single or three phase.
Specifications are subject to change without notice.
Refrigerant:
R-22, R410A is available
Cooling BTU’s:
148,800 (NOMINAL)
Compressors:
(2) Hermetically Sealed Scroll
Unit Capacity @ 50% RH:
59.52 lbs./hr. moisture removal
Unit Capacity @ 60% RH:
74.90 lbs./hr. moisture removal
Nominal CFM:
4500+
Dimensions
Height:
59.25”
Width:
32.0”
Depth:
39.5”
Water Loop In:
1.0”
Water Loop Out:
1-1/2”
Weight:
730 lbs.
Filter Size:
36”x38”
FLS Condenser
#206
Electrical Requirements STANDARD UNIT-DUAL COMPRESSORS 208-230-1-60 Single Phase
Compressor RLA:
27.9 each
Compressor LRA:
176.00 each
Fan Motor FLA:
2-5.0**
Fan Motor LRA:
2-38.3*
Total Unit:
65.8
MCA:
80.0
Max. Fuse:
100.0
Controls are 24 Volts off unit.
Supply:
Top, Right or Left
Return:
Left or Right
Belt Driven Blower Models, or 3 Phase call for electrical specs
*These models are dual compressor units & come standard with direct driven twin blowers. Fan motor FLA & RLA shows per each motor. All HCD models come with two compressors, separate refrigerant systems.
Plumbing is located front left, electrical panel front right, and compressors are on bottom right hand side of unit. 36”’ Clearance is required from front and bottom right hand side of unit for access and serviceability.
EPS is the home of DRY-AIR & VERI-DRY. We provide Design, Engineering, Consulting and Manufacturing for Residential and Commercial Indoor Swimming Pool Applications.