| EM Series 1-25 Ton Features
EM072-180 Vertical Dimemsions
EM072-140 Horizontal Dimensions
EM170-242 Horizontal Dimensions
EM144-360 Vertical Dimensions
EM 024 Specification Sheet
EM 036 Specification Sheet
EM 048 Specification Sheet
EM 060 Specification Sheet
EM 072 Specification Sheet
EM 096 Specification Sheet
EM 120 Specification Sheet
EM 144 Specification Sheet
EM 150 Specification Sheet
EM 168 Specification Sheet
EM 170 Specification Sheet
EM 210 Specification Sheet
EM 240 Specification Sheet
EM 300 Specification Sheet
EM 360 Specification Sheet
|
|
GENERAL
Furnish
and install where shown on plans, EM Series self-contained
packaged air-conditioning dehumidification unit. Capacities,
models and unit arrangement shall be as shown on the unit schedule
and the contract drawings. Units shall be listed for UL and
CUL. Units shall conform to ANSI/UL standard 1995. Each unit
shall be completely factory assembled, piped, wired, and tested.
Units shall be leak tested and charged with a full operating
charge of Refrigerant 22. Installation and maintenance manuals
and wiring diagrams shall be supplied with each unit. Factory
tested shall include, but not limited to: complete run check
of all electrical components and safeties, including proper
control sequencing; pressure test of refrigerant coils and
condensers; leak check of completed refrigerant circuits; leak
check of completed water circuit; compressor run check.
The units shall be designed to operate with entering fluid temperatures between
50°F (10°C) and 110°F (43.3°C) in cooling
REFRIGERATION
CIRCUITS
All
units shall contain sealed refrigerant circuits including
hermetic compressors, thermal expansion valve metering
devices, finned tube air-to-refrigerant exchangers,
refrigerant reversing valves and service ports. Compressors
shall be high efficiency, designed for heat pump duty,
internally spring isolated (except for scroll type
compressors) for maximum sound attenuation and mounted
on rubber vibration isolators.
Compressor motors shall be equipped with overload protection. Refrigerant
reversing valves shall be pilot operated sliding piston type with replaceable
encapsulated magnetic coils energized only during the cooling cycle.
The finned tube coil shall be constructed of lanced aluminum fins not
exceedi ng fourteen fins per inch bonded to rifled copper tubes in a
staggered pattern not less than three rows deep and have a 450 PSIG (3100
kPa) working pressure. The coaxial water-to-refrigerant heat exchangers
shall be constructed of a convoluted copper (optional cupronickel) inner
tube and steel outer tube with a designed refrigerant working pressure
of 450 PSIG (3100 kPa) and a designed water side working pressure of
no less than 400 PSIG (2750 kPa).heat.
CASING & CABINET
(Cabinet
is available in stainless steel as an option)
Galva-LumThe cabinet shall be fabricated from
heavy-gauge galvanized steel and aluminum.
The interior shall be insulated with ½” (12/7mm)
thick, multi density, coated, glass fiber.
All units shall allow sufficient service access
to replace the compressors without unit removal.
Two blower and two compressor compartment access
panels shall be removable with supply and return
ductwork in place. A duct collar shall be provided
on the supply air opening of all vertical units.
A 2” (50.8mm) return air filter rack/duct
collar with 1” (25.4mm) thick filters
shall be provided with each unit. Vertical
units shall have an insulated divider panel
between the air handling section and the compressor
section to minimize the transmission of compressor
noise, and to permit operational service testing
without air bypass.
PIPING
Supply,
return water and condensate drain connections
shall be copper or brass female pipe thread fittings
and mounted flush to cabinet exterior.
ELECTRICAL
Controls
and safety devices will be factory wired and mounted
within the unit. Controls shall include fan relay(s),
compressor contractors, 24V transformer, reversing
valve coils and a solid state lock-out control circuit
which includes diagnostic LED’s, low pressure
bypass time delay, anti-short cycle time delay and
random start time delay. When the safety controls
are activated the lock-out circuit must allow one
intelligent reset to avoid nuisance trips. Subsequent
lock-outs must be reset at the thermostat or main
circuit breaker to prevent compressor operation during
fault conditions. A lockout indicating terminal shall
be provided in the low voltage circuit. Safety devices
include a low-pressure cutout set at 20 PSIG (140
kPa) for loss of charge protection (a freeze stat
used for loss of charge protection is not acceptable)
and a high-pressure cutout control set at 380 PSIG
(2600 kPa). An optional condensate overflow switch
shall be factory installed to stop compressor operation
to prevent drain pan overflow. An optional energy
management relay to allow unit control by an external
source shall be factory installed.
FAN MOTOR & ASSEMBLY(S)
The
fan(s) shall be belt driven DWDI forward curved
type with dynamically balanced wheel(s). The
housing(s) and wheel(s) shall be designed for
quiet low velocity operation. The fan housing(s)
shall be removable from the unit without disconnecting
the supply air ductwork for servicing of the
fan motor(s)
The
fan motor(s) shall be 1725 or 3450 RPM 56 frame
sealed ball bearing type. The motor(s) shall
be permanently lubricated and have thermal
overload protection.
|